Rayshen

FFU - Fan Filter Unit

FFU - Fan Filter Unit

Our products are fully configured before shipping, to ensure that facility management staff can independently understand and operate the equipment, as well as perform basic troubleshooting and maintenance. This manual has been created for that purpose.

Friendly reminder: If the equipment is operating normally without any faults, please do not tamper with the control panel.

ModelGF24ACSF24ACGF24DCSF24DCGF44DCSF44DC
Dimensions
(mm)
1175*575*1801175*575*2651175*1175*320
Weight
(kg)
161935
Noise
(dB)
605555
(1)Total Static Pressure (Pa)190280320
MaterialCasingGalvanized AluminumStainless SteelGalvanized AluminumStainless SteelGalvanized AluminumStainless Steel
Impeller Steel-Aluminum AlloyFull Aluminum
(2)Operating Air Speed with filter
(m/s )
0.45
Maximum Air Volume without filter
(CMH)
130020003800
Working Air Volume  with filter (CMH)Low850300-1200 (Stepless Speed Control)600-2400 (Stepless Speed Control)
Medium950
High1050
Motor Power
 (W)
190150300
Max RPM105012001400
TypeAC Induction MotorDC Brushless Motor
Efficiency ClassIE2IE4
(3)
Control Mode
Single ControlSingle/Group Control
(4)
Start Mode
Direct Switch StartSoftware / Control Panel Start
Safe Operating Voltage200V-240V
Safe Operating Temperature
(°C)
<55℃<65℃
(5)Average Daily Power Consumption
 (kWh)
3.841.924.32
Note: Custom sizes available upon request.     

 

Explanation
(1) Total Static Pressure: Indicates the total pressure that the FFU can provide under working conditions, including system resistance.
(2) Operating Air Speed with filter: The airflow speed of the FFU after the filter is installed.
(3) Control Modes:
Single Control: Each FFU operates independently, suitable for small-scale systems.
*Group Control: Multiple FFUs operate in unison, suitable for large-scale cleanrooms, improving management efficiency.
(4) Startup Modes:
Direct Switch Start: Manually turn on/off, each FFU operates independently.
*Software Automatic Control Start: After connecting the FFU to the control panel, the control panel can be used to set automatic start/stop parameters.
*Control Panel Start: After connecting the FFU to the control panel, it can be manually started via the control panel.