Rayshen

We are a technology driven company focused on the design, engineering, and manufacturing of high performance cleanroom and contamination control equipment. Our solutions are built for mission critical environments across a range of industries, including Pharmaceuticals, Biotechnology, Hospitals, Semiconductors, Electronics, Food Processing, and other sectors where cleanliness and control are non-negotiable.

Semi-Conductor

FFU - Fan Filter Unit

Our products are fully configured before shipping, to ensure that facility management staff can independently understand and operate the equipment, as well as perform basic troubleshooting and maintenance. This manual has been created for that purpose.

Friendly reminder: If the equipment is operating normally without any faults, please do not tamper with the control panel.

SNItemsSpecifications
1Dimensions (mm)1175*575*180
2Weight (kg)16
3Noise (dB)60
4(1)Total Static Pressure (Pa)190
5MaterialCasingGalvanized Aluminum
6ImpellerSteel-Aluminum Alloy
7(2)Operating Air Speed with filter(m/s )0.45
8Maximum Air Volume without filter (CMH)1300
9Working Air Volume with filter (CMH)Low850
10Medium950
11High1050
12MotorPower (W)190
13Max RPM1050
14TypeAC Induction Motor
15Efficiency ClassIE2
16(3)Control ModeSingle Control
17(4)Start ModeDirect Switch Start
18Safe Operating Voltage200V-240V
19Safe Operating Temperature (°C)<55℃
20(5)Average Daily Power Consumption (kWh)3.84

 

Explanation
(1) Total Static Pressure: Indicates the total pressure that the FFU can provide under working conditions, including system resistance.
(2) Operating Air Speed with filter: The airflow speed of the FFU after the filter is installed.
(3) Control Modes:
Single Control: Each FFU operates independently, suitable for small-scale systems.
*Group Control: Multiple FFUs operate in unison, suitable for large-scale cleanrooms, improving management efficiency.
(4) Startup Modes:
Direct Switch Start: Manually turn on/off, each FFU operates independently.
*Software Automatic Control Start: After connecting the FFU to the control panel, the control panel can be used to set automatic start/stop parameters.
*Control Panel Start: After connecting the FFU to the control panel, it can be manually started via the control panel.

Certificate Name

FFU - Fan Filter Unit